Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
35
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Modbus Cradle Communication Module (CCM)
The optional Modbus cradle communication module (CCM) is installed adjacent to the circuit breaker
cradle and is the gateway between the Modbus network and the Modbus BCM. The Modbus CCM
provides circuit breaker cradle status including connected position (CE), disconnected position (CD) and
test position (CT). The CCM monitors the communication parameters of the Modbus BCM and trip unit
when it detects a circuit breaker being racked from the cradle. When the circuit breaker is reinstalled or a
spare circuit breaker is installed and racked into the cradle, the CCM automatically downloads the
address, baud rate, and parity into the BCM. This capability allows a circuit breaker to be replaced
without the need to manually configure the communication parameters in the Modbus BCM.
The CCM maintains an event log of the date and time of the last circuit breaker transition. In order to
aid system communication troubleshooting, the CCM has visual indication of the module’s operating
status by means of two LEDs.
Cradle Communication
Module (CCM)
Table 30: Characteristics
Circuit Breaker Identification
z ID Code, Address
z Size, Rating, Performance
z Type of Trip Unit
z Type of Long-Time Rating Plug
Status Indication
z ON/OFF Indication
z Connected/Disconnected/Test Pos.
z Ready-to-Close
z Fault Trip
Controls
Opening/Closing
Settings
Circuit
Breaker and
Trip Unit
APH
z Reading of Settings on Rotary Switches XXX
z Fine Settings in the Range Imposed by the Rotary Switches X X
z Setting of Protection and Alarms XX
z Customized Alarm Programming X
Operating and Maintenance Aids
Reading of Protection and Alarms
Standard X X
Set X X
Customized X
Reading of Measurements
Current X X X
Voltages, frequency, power, etc. X X
Power quality: Fundamentals and harmonics X
Waveform Capture X
Histories
History of trips and alarms
1
1
Up to 10 trips and 10 alarms.
XX
Log of trips and alarms X
Indicators
Contact wear, counters, etc. X X
Maintenance record X