Universal Remote Control MX-880Z - SPECS SHEET Informacje Techniczne Strona 20

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 180
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 19
© 2000–2014 Schneider Electric
All Rights Reserved
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
20
05/2014
Overview of Micrologic Trip Systems
All Masterpact™ circuit breakers are equipped with the Micrologic trip system to protect power circuits
and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense
current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable
rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault
current protection required in the electrical system. If current exceeds a set value for longer than its set
time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote
indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity
of service and energy management. Micrologic trip units can be changed on-site.
Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic
component used in all Micrologic trip units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are
managed by an independent microprocessor.
Masterpact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit
adjustments set at their lowest settings. Actual settings required for a specific application must be
determined by a qualified consultant or plant engineer. A coordination study is recommended to
provide coordination between all circuit breakers in the distribution system.
Thermal Imaging
The thermal imaging function protects the cables or bus bars from overheating in case of low
amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load,
intermittent ground faults, or subsequent closing after a fault.
Traditional electronic protection does not protect against repetitive faults because the duration of each
overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each
overload involves a temperature rise in the installation, the cumulative effect of which could lead to
overheating of the system.
The thermal imaging function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and,
therefore, the reaction of the trip unit will be closer to the real heating of the power network system.
After tripping, the function will also reduce the time delay when closing the circuit breaker on an
overload.
Model
LS0 LI LSI LSIG
Long-Time +
Short-Time +
Zero Delay
Long-Time +
Instantaneous
Protection
Long-Time + Short-Time
+ Instantaneous
Protection
Long-Time + Short-Time
+ Instantaneous
Protection + Equipment
Ground-Fault Protection
(IEC Rated)
(UL Listed and
ANSI Certified)
(UL LIsted, ANSI
Certified, IEC Rated)
(UL LIsted, ANSI
Certified, IEC Rated)
Basic Trip Unit
A Trip Unit
P Trip Unit
H Trip Unit
2.0
2.0A
3.0
3.0A
5.0
5.0A
5.0P
5.0H
6.0A
6.0P
6.0H
Figure 6: P Trip Unit with Power Metering
Przeglądanie stron 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 179 180

Komentarze do niniejszej Instrukcji

Brak uwag